Variable area flowmeters (Rotameters) theoretically involve indication
errors when the operating condition deviate from the design condition.
However, these errors can be compensated by calculations. The calculation
procedure by fluid types are shown below.

IN CASE OF LIQUID MEASUREMENT
The liquid density change from the design condition produces indication
error.
< Compensation Calculation Example >
|
Original design condition of flowmeter |
| |
Fluid : Water
Design density : 1.0 g/cm3 |
| Actual process condition |
| |
Fluid : Alcohol
Design density : 0.8 g/cm3 |
| Indication of flowmeter : 10m3/h |

Actual flow rate of Alcohol = 10 × 1.134 = 11.34 m3/h

IN CASE OF GAS FLOW MEASUREMENT
| In Gas Flow Measurement, |
| |
Density of the ygas to be measured (under Normal condition, 0°C,1atm)
Operating pressure
Operating temperature |
as the factors of compensation.
|
< Compensation Calculation Example >
| Original design condition of flowmeter |
| |
Fluid : Air
Design density : 1.293kg/m3(Normal) |
Design pressure : 0.2MPa
Design temperature : 20°C
Actual process condition |
| |
Fluid : CO2 Gas
Design density : 1.977 kg/m3(Normal)
Actual operating pressure : 0.4MPa
Actual operating temperature : 50°C |
| Indication of flowmeter : 5m3/h(nor) |


Actual flow rate of CO2 gas = 5 × 1.010 = 5.05 m3/h(nor)
IN CASE OF (SATURATED) STEAM FLOW MEASUREMENT
Correction calculation is done by the density of the steam to be measured
Actual Flow rate = Indicated flow rate × Correction coefficient
 |
Density correction coefficient |
 |
Density of actual steam (kg/m3) |
 |
Design density (kg/m3) |
|
|
< Compensation Calculation Example >
| Original design condition of flowmeter |
| |
Fluid : Steam
Design density : 5.163kg/m3 |
Design pressure : 0.902MPa
Design temperature : 180°C
Actual process condition |
| |
Fluid : Steam
Design density : 2.549kg/m3
Actual operating pressure : 0.3479MPa
Actual operating temperature : 150°C |
Indication of flowmeter : 10 t/h
The steam density in operating condition is to be referred to Steam Table. |

Actual Steam Flow rate at 150°C = 10 t/h × 0.703 = 7.03 t/h
|